| Sign In | Join Free | My burrillandco.com |
|
| Ask Lasest Price | |
| Brand Name : | ZONCN |
| Model Number : | Z2400-37G/45P |
| Certification : | CE |
| Payment Terms : | T/T,Western Union,Paypal |
| Supply Ability : | 100000 units a month |
| Delivery Time : | 7-30 work day |



| Item | Z2000 | |
| Standard Function | Control mode | Senseless flux vector control(SFVC) ; Voltage/Frequency (V/F) control |
| Maximum frequency | Vector control: 0-320Hz ; V/F control: 0-3200Hz | |
| Carrier frequency | 1-16kHz ; The carrier frequency is automatically adjusted based on the load features | |
| Input frequency solution | Digital setting: 0.01Hz ; Analog setting: maximum frequency x 0.025% | |
| Startup torque | G type: 0.5Hz/150%(SFVC) ; P type: 0.5Hz/100% | |
| Speed range | 1:100 | |
| Speed stability accuracy | ±0.5% | |
| Overload capacity | G type: 60s for 150% of the rated current, 3s for 180% of the rated current. P type: 60s for 120% of the rated current, 3s for 150% of the rated current. | |
| Torque boost | Auto boost ; Customized boost 0.1%-30.0% | |
| V/F curve | Line V/F curve; Multi-point V/F curve; N-power V/F curve | |
| V/F separation | Two types: complete separation; half separation | |
| Ramp mode | Straight-line ramp ; S-curve ramp ; Four groups of acceleration/deceleration time with the range of 0.0-6500.0s | |
| DC braking | DC braking frequency : 0.0Hz to maximum frequency Braking time: 0.0~100.0s Braking action current value: 0.0%~100.0% | |
| JOG control | JOG frequency range: 0.00~50.00Hz JOG acceleration/deceleration time: 0.0~6500.0s | |
| Onboard multiple preset speeds | It implements up to 16 speeds via the simple PLC function or combination of X terminal states. | |
| Onboard PID | It realizes process-controlled closed loop control system easily | |
| Auto voltage regulation(AVR) | It can keep constant output voltage automatically when the mains voltage changes. | |
| Auto voltage/ Over current stall control | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/over current | |
| Rapid current limit | It helps to avoid frequent over current faults of the AC drive | |
| Torque limit and control | It can keep constant output voltage automatically when the mains voltage changes | |